POSTO PRIMÁRIO SIMPLIFICADO
Concessionária Bandeirante _______________________________________________
| TRAFO | ELO | TENSÃO | DISJ | FASE | NEUTRO | T-N | TUBO |
| 45 | 3H | 220/127V 380/220V |
120 A 70 A |
50,0mm 35,0mm |
50,0mm 35,0mm |
25,0mm 25,0mm |
3" (80mm) 3" (80mm) |
| 75 | 5H | 220/127V 380/220V |
200 A 120 A |
120,0mm 50,0mm |
120,0mm 50,0mm |
70,0mm 25,0mm |
4" (100mm) 3" (80mm) |
| 112,5 | 6K | 220/127V 380/220V |
300 A 175 A |
240,0mm 120,0mm |
240,0mm 120,0mm |
120,0mm 70,0mm |
4" (100mm) 4" (100mm) |
| 150 | 8K | 220/127V 380/220V |
400 A 225 A |
2x120,0mm 185,0mm |
2x120,0mm 185,0mm |
120,0mm 95,0mm |
2x4" (100mm) 4" (100mm) |
| 225 | 10K | 220/127V 380/220V |
600 A 350 A |
2x240,0mm 2x120,0mm |
2x240,0mm 2x120,0mm |
240,0mm 120,0mm |
2x4" (100mm) 2x4" (100mm) |
| 300 | 15K | 220/127V* 380/220V |
800 A 450 A |
2x240,0mm 2x185,0mm |
2x240,0mm 2x185,0mm |
240,0mm 120,0mm |
2x4" (100mm) 2x4" (100mm) |
* = Cabos XPLE ou EPR 90 (300KVA-220/127V)
A malha de aterramento geral deverá ser bitola mínima de 50,0mm e 3 hastes 5/8"x2400mm
e a resistência máxima de 10 Ohms em qualquer época do ano.